Noise, planning permission and where the outdoor unit goes

The 37 dB noise limit your installer has to check, the planning rules for heat pumps in each UK nation, and how to choose a spot for the outdoor unit.

Last reviewed 16 November 2026 7 min read7 sources

In England and Wales, an air source heat pump on a house normally needs no planning application if the calculated noise at your neighbours' nearest windows is 37.0 dB or below and a short list of other conditions is met. That limit comes from MCS 020 a) Issue 1.1, the noise calculation your installer has to carry out (1.2, step 8). Scotland and Northern Ireland have their own rules, which are set out further down.

"Permitted development" is the term for work that has planning permission granted nationally, so you don't apply to the council. It only applies if every condition is met. MCS 020 a) says plainly that passing the noise check is not enough on its own (1.3).

How the 37 dB check works

The installer works out how loud the heat pump will be at an "assessment position": a point 1 m outside the middle of a door or window to a habitable room of a neighbouring home, such as a bedroom or living room (section 2). A kitchen used only for cooking does not count, but a kitchen you also eat or sit in does. Bathrooms, toilets, halls, corridors, laundry rooms and utility rooms do not count. If the heat pump goes on a block of flats, the other flats in the block count as neighbours, but your own flat does not.

The calculation starts from the heat pump's sound power level, a figure from the manufacturer's data. It then allows for hard surfaces near the unit, the distance to the window, and any solid wall or fence in between, and gives a sound level in dB(A) at the window (steps 3 to 7). Every assessment position has to come out at 37.0 or below. The installer should check neighbours on all sides and on upper floors, because the nearest window is not always the loudest (step 2). The figure for "low noise mode" may not be used (step 3). A unit with more than three hard surfaces around it, such as one in a small lightwell, cannot pass (step 4). Our installer guide to the MCS 020 a) noise assessment has the equation and the standard's own worked example.

You should get a copy of the completed calculation (1.7). Keep it with your house documents.

Here is a worked example of our own, using the method in the standard. A heat pump with a sound power level of 58 dB(A) stands on the ground against the house wall, which counts as two reflecting surfaces. A neighbour's bedroom window is 5 m away with nothing in between. That gives 39.0 dB(A), which fails. Moving the heat pump to 8 m from the window gives 35.0, which passes. So would keeping it at 5 m behind a solid brick garden wall that hides the window completely, which takes 10 dB off and gives 29.0.

When a position fails the check

MCS's guidance on mitigating heat pump noise (section 5) lists what an installer can try before you need a planning application:

  • move the heat pump more than 1 m from walls and other hard surfaces;
  • choose a model with a lower sound power level;
  • add a solid wall or fence with no gaps that hides the neighbour's window from the top of the unit, or move the unit or the barrier so it does;
  • check the right windows were assessed.

Plants and hedges do not count as a barrier, and neither does a fence with gaps or one in poor repair. If a wall or fence was part of the calculation, the guidance says to replace it quickly with an equivalent if it is ever taken down (section 3). Ask your installer to tell you in writing if your result depends on one.

If none of that works, you would need to apply for planning permission for that position.

Planning conditions in England and Wales

The Planning Portal lists the conditions for England. The installation must comply with MCS 020 a). The outdoor unit, including any housing, can be up to 1.5 cubic metres on a house and 0.6 on a block of flats. A detached house can have two heat pumps, other houses one. There is no longer a minimum distance from the boundary. The heat pump must not be used only for cooling, so an air-to-air unit that also heats can qualify. Permitted development does not apply:

  • on a pitched roof, or within 1 m of the edge of a flat roof;
  • within the grounds of a listed building;
  • in a conservation area or World Heritage Site, on a wall or roof facing a road, or nearer the road than the house;
  • elsewhere, above ground floor level on a wall facing a road;
  • where there is already a wind turbine at the property.

A council can also remove these rights in a particular area, so if you are unsure, ask your council before you commit to a position.

The Welsh Government changed its rules on 1 June 2026. They now match England closely: MCS 020 a), a 1.5 cubic metre limit, two units on a detached home and one on others, nothing on a pitched roof or within 1 m of the edge of a flat roof, nothing on a listed house, and the same restrictions on road-facing walls and in conservation areas.

Planning conditions in Scotland and Northern Ireland

In Scotland, Circular 1/2024 (Class 6H) allows one air source heat pump on a house or in its grounds. It must meet the MCS planning standards for air source heat pumps or an equivalent. A unit fixed to the house can stick out no more than 1 m from the wall or roof, and a unit in the grounds can be no more than 3 m high and not forward of a wall facing a road. In a conservation area, a unit on the house must be at ground floor level on the rear wall. Permitted development does not apply in a World Heritage Site or within the grounds of a listed building. There is no boundary distance. A building warrant may also be needed, so ask your council's building standards team.

Northern Ireland has allowed heat pumps as permitted development since 4 July 2023, according to the Department for Infrastructure. The conditions in SR 2023/95 (Class G) are:

  • one air source heat pump within the grounds;
  • no part within 1 m of the boundary with another home's grounds;
  • not forward of a road-facing wall that forms the front or side of the original house;
  • not on a roof, and the outdoor unit no more than 3 m high;
  • in a conservation area or World Heritage Site, no part facing onto and visible from a road;
  • within the grounds of a listed building, only where listed building consent has already been granted;
  • compliance with MCS planning standards (defined there as MCS 020) or an equivalent.

You may also need building control approval. If any condition is not met, ask your council's planning department before you agree a position.

Choosing a good spot for the unit

The noise rules protect neighbours. Your own comfort and the heat pump's efficiency need a bit more thought. MCS's mitigation guidance (sections 2.1 to 2.3) suggests:

  • avoid corners, enclosed yards and alcoves, which make the unit sound louder;
  • face the fan away from neighbours and from your own bedrooms where possible;
  • don't fix the unit to a wall next to a bedroom, or to a structure that carries vibration, and use anti-vibration feet, pads or rubber grommets on wall brackets;
  • remember quiet modes cut noise but can also cut heat output, slow hot water recovery and lower efficiency, so they are not a fix for a poor position;
  • schedule hot water heating away from the hours people sleep.

Give the unit the clearance for airflow the manufacturer's manual asks for. A unit boxed in by fences or a decorative cover, or facing a wall, can pull its own cold exhaust air back in and work harder. It also needs a solid, level base with somewhere for defrost water to drain. Short, well-insulated pipes to the house and cylinder help too.

The guidance also suggests talking to neighbours before the work, which tends to head off complaints later. If a heat pump becomes noisier over time, the usual causes are a loose or failing part, debris in the fan, missed servicing, or a barrier that has been removed (section 6). Raise it with your installer, as installers and consumer protection explains.

Sources

What this guide relies on, and the date we read each one. Rules, prices and standards change, so check the source before you act on a figure.

  1. MCS, MCS 020 a) Issue 1.1 Air Source Heat Pump Sound Calculationmcscertified.com, read 16 November 2026
  2. MCS, Installation Guidance for Mitigating Noise from Air Source Heat Pumps (September 2025)mcscertified.com, read 16 November 2026
  3. Planning Portal, Planning permission for an air source heat pumpplanningportal.co.uk, read 16 November 2026
  4. Welsh Government, Planning permission for heat pumpsgov.wales, read 16 November 2026
  5. Scottish Government, Circular 1/2024 householder permitted development rights, Class 6Hgov.scot, read 16 November 2026
  6. legislation.gov.uk, Planning (General Permitted Development) (Amendment) Order (Northern Ireland) 2023, SR 2023/95legislation.gov.uk, read 16 November 2026
  7. Department for Infrastructure, Changes to permitted development rights for domestic heat pumpsinfrastructure-ni.gov.uk, read 16 November 2026

Quick answers on this subject

Still have a question?Ask it and get an answer with sources. No sign-up needed.

Guidance only. It is not a substitute for a survey or a professional design for your home.