Hot water cylinder sizing for heat pumps under MCS

The MCS hot water demand rule, cylinder and reheat sizing under BS EN 12831-3 and the CIBSE guides, the MGD 007 minimums, and what HSE and CIBSE say about legionella in homes.

Last reviewed 16 November 2026 7 min read14 sources

MIS 3005-D sets daily hot water demand at 45 litres times N, where N is the greater of bedrooms plus one and the known number of occupants (MIS 3005-D:2025 §3.5.2; Issue 3.0 §5.6.2). For a new build, MIS 3005-D:2025 adds, use bedrooms plus one. A three-bedroom house with two people in it is designed for four, so 180 litres a day.

That figure is a demand, not a cylinder volume. The cylinder is specified from the demand and the heat pump's capacity, with MGD 007 named for size guidance and available space acknowledged as a limit (MIS 3005-D:2025 §3.5.3; Issue 3.0 §5.6.3).

What else MIS 3005-D requires

  • The coil follows the heat pump or cylinder manufacturer's recommendations, and cylinders labelled to the Hot Water Association's HWA 002:2020 satisfy this (MIS 3005-D:2025 §3.5.4; Issue 3.0 §5.6.5).
  • With a cylinder, the heat pump shall be capable of at least 55°C flow at design conditions (MIS 3005-D:2025 §3.5.5; Issue 3.0 §5.6.6).
  • An existing cylinder may be reused if its insulation and connected pipes are brought up to new-installation standard, it is fit for purpose mechanically, and its size meets the heat pump manufacturer's requirement (MIS 3005-D:2025 §3.5.6; Issue 3.0 §5.6.7).
  • Issue 3.0 alone requires the reheat time to be agreed with the customer (§5.6.4); MIS 3005-D:2025 has no equivalent clause.

Before installation, the daily hot water demand and the cylinder specification with its recovery rate are set out in writing, for the installer under MIS 3005-D:2025 §3.8.1 and for the customer under Issue 3.0 §5.9.2.

How BS EN 12831-3 sizes a cylinder

BS EN 12831-3:2017 sizes a hot water system by comparing two cumulative curves over a day, in one-minute steps (§5.1). The needs curve adds up the energy drawn off; the supply curve adds up what the heat source and store can deliver. The system is adequate while the supply curve stays at or above the needs curve. You fix one of heat input or storage volume and solve for the other. Approved Document L points to BS EN 12831-3 for hot water sizing and says systems should not be significantly oversized (2021 edition, paragraph 5.11; 2026 edition, paragraph 4.15, which also names the DHDG).

Annex B gives defaults where there are no national values: daily profiles adapted from EN 50440, a delivery temperature of 42°C and a cold feed of 10°C (Table B.6), and 40 to 70 litres per person per day for single-family dwellings (Table B.5). For a heat pump it allows a 4 minute start-up lag (Table B.10). A mixed tank with an internal coil keeps only about 96% of its volume at set temperature (Table B.7), and must hold back a minimum reserve while it recharges (§6.4.2.4).

The CIBSE simplified method

The CIBSE Domestic Heating Design Guide (DHDG) §4.5.1 reduces this to two choices: a cylinder volume that covers a day's typical use with one extended reheat, and a reheat time. Its Table 4-1, based on the CIPHE minimum sizing method, assumes up to 40 litres per person per day at 42°C, taking the larger of (bedrooms plus bathrooms) times 40 and occupants times 40. The volume needed rises as the stored temperature falls.

Property in DHDG Table 4-1At 60°C (litres)At 55°CAt 50°C
1 bedroom, 1 bathroom110140193
2 bedrooms, 1 bathroom165210289
3 bedrooms, 1 bathroom220280385
3 bedrooms, 2 bathrooms275350481
4 bedrooms, 2 bathrooms330419577

For the target temperature, Note 510 of the CIBSE and HPA heat pump guide says to use 60°C if the heat pump can reach it efficiently at the outdoor design temperature, 55°C otherwise, and 50°C only where hot water will still reach the taps at 50°C within a minute as BS 8558 requires. For multiple reheats a day, Note 520 points to BS EN 12831-3 software, which can justify a smaller cylinder. The DHDG says the same for unusual demand.

Reheat time and the coil

Cylinder makers quote reheat at 80°C primary flow, as BS EN 12897 requires, which heat pump temperatures won't match. The DHDG recommends a cylinder with reheat figures at the design flow temperature, such as one tested to HWA 002.

With hot water priority, the DHDG (§4.5.1.2) and Note 521 of the heat pump guide set the minimum coil rating from the space heating load, no higher than the heat pump's capacity, and read the reheat time from DHDG Table 4-2, measured from 42°C to the target. If reheat runs past 2 hours, improve fabric and airtightness so rooms don't cool meanwhile. Past 8 hours, reconsider priority control or use a separate heat source. A DHDG example: a 289 litre cylinder held at 50°C, reheated at 55°C flow in a home with a 4.2 kW heating load, takes a 4 kW coil and about 6 hours.

MGD 007 §2.2 gives the arithmetic behind its own sizes: minutes equals litres times temperature rise divided by 14.3 times kW. On that basis, heating 200 litres from 10°C to 50°C at 4 kW takes 200 × 40 / (14.3 × 4), about 140 minutes.

Minimum cylinder sizes in MGD 007

MGD 007 Issue 1.0, dated 14 July 2021, bases its guide on BS 6700. It allows 45 litres per occupant without rapid reheat, falling to 35 litres for heat pumps of 10 to 15 kW or more with suitable coils, and sets minimums by heat pump size:

Heat pump capacityOne bathroom (litres)Two bathrooms (litres)
3 kW122260
6 kW88200
8 kW73131
10 kW70130
15 kW and over70130

The smaller the heat pump, the larger the minimum. These minimums sit well below the DHDG's Table 4-1 volumes, which aim to hold a full day's use.

The hot water factor in MCS 031 a) rose from 1.7 to 1.9

MCS 031 a) Issue 5.0 and MCS 031 a):2025 Issue 2.0, both dated 5 December 2025, changed the hot water performance factor from 1.7 to 1.9. In step (n) of the estimate, hot water electricity is the EPC hot water demand divided by 1.9, or by 2.2 where a ground source heat pump heats the water. The RHPP field trial analysis (March 2017) found a median SPF at H2 of 2.31 for air source hot water (284 sites) against 2.74 for space heating (292 sites); the report notes both may be over-estimated by 4 to 7%.

Step (o) prices the immersion pasteurisation cycle as F × volume × 10 × 4,200 / 3,600,000 kWh a year, where F is 52 weekly, 365 daily, and 0 if the heat pump does it or it isn't needed. For a 200 litre cylinder that's about 121 kWh a year weekly and about 852 kWh daily.

Legionella and scalding

MIS 3005-D:2025 §3.5.7 (Issue 3.0 §5.6.8) says hot water systems shall incorporate a means to prevent bacterial growth, and that where this is periodic pasteurisation, a risk assessment can help set the frequency.

DHDG §4.9.1 states that HSE recommends, as an important control in dwellings, raising all stored water to at least 60°C for at least an hour, at least once a week. On that basis it allows an owner-occupied home where the designer judges the risk minimal to store below 60°C, provided a routine raises the whole cylinder, and any secondary circulation, to 60°C for an hour. Every system should be capable of heating all stored water to 60°C, with an immersion or other heat source where the heat pump can't. Otherwise a competent person's risk assessment sets the routine.

For rented homes HSE's page for landlords places a duty to assess the risk, says a simple assessment is usually enough, and names temperature as the most reliable control, with the cylinder storing at 60°C. Its hot and cold water page asks for 50°C at outlets within a minute. Full technical guidance is in HSG274 Part 2.

Against scalding, the DHDG (§4.9.2) and the heat pump guide recommend thermostatic mixing at or near each outlet, NSF Type 2 or better, set to 46°C for baths, 41°C for showers and basins and 38°C for bidets.

Unvented cylinders and Approved Document G

In England, requirement G3(3) says stored water must never exceed 100°C and any discharge from safety devices must be carried somewhere visible and safe. Approved Document G (2015 edition with 2024 amendments) sets out how:

  • At least two independent safety devices beyond the thermostat, typically a non-self-resetting energy cut-out and a temperature, or temperature and pressure, relief valve fitted directly on the vessel (paragraphs 3.17, 3.18 and 3.38). Each heat source needs its own cut-out (3.33), so a heat pump coil and an immersion each have one.
  • A system up to 500 litres and under 45 kW should be a proprietary unit or package meeting a standard such as BS EN 12897 (3.22).
  • The relief valve discharges through a short metal pipe (D1) to a tundish in the same space, with no more than 600 mm of pipe between them; the pipe from the tundish (D2) drops at least 300 mm vertically, then falls at least 1 in 200, and is sized up as its length grows (3.50 to 3.58).
  • Installing an unvented system is notifiable building work. Notify building control before starting, unless the installer is registered with a competent person scheme for this work and self-certifies (3.41 and 3.42).
  • In a new dwelling, or one formed by a change of use, hot water to a bath is limited to 48°C (G3(4) and 3.65).

DHDG §4.5.3 summarises the same arrangement, adding the expansion vessel or internal air gap.

Sources

What this guide relies on, and the date we read each one. Rules, prices and standards change, so check the source before you act on a figure.

  1. MCS, MIS 3005-D:2025 Heat Pump Design Standard, Issue 2.0mcscertified.com, read 16 November 2026
  2. MCS, MIS 3005-D Issue 3.0 (alongside MIS 3005-D:2025), The Heat Pump Standard (Design)mcscertified.com, read 16 November 2026
  3. BSI, BS EN 12831-3:2017 Energy performance of buildings, Method for calculation of the design heat load, Part 3 Domestic hot water systems heat load and characterisation of needsknowledge.bsigroup.com, read 16 November 2026
  4. CIBSE, Domestic Heating Design Guide (2026), version 2026-02cibse.org, read 16 November 2026
  5. CIBSE and HPA, Domestic Heat Pump Design and Installation Guide (2026)cibse.org, read 16 November 2026
  6. MCS, MGD 007 Heat Pump Reference Information and Tools, Issue 1.0mcscertified.com, read 16 November 2026
  7. MCS, MCS 031 a):2025 Issue 2.0, Hydronic Heat Pump Pre-sale Information and Calculationsmcscertified.com, read 16 November 2026
  8. MCS, MCS 031 a) Issue 5.0, Hydronic Heat Pump Pre-sale Information and Performance Calculationmcscertified.com, read 16 November 2026
  9. HSE, Hot and cold water systemshse.gov.uk, read 15 November 2026
  10. HSE, Legionella and landlords' responsibilitieshse.gov.uk, read 15 November 2026
  11. HSE, HSG274 Legionnaires' disease technical guidancehse.gov.uk, read 15 November 2026
  12. RAPID-HPC for BEIS, Final report on analysis of heat pump data from the RHPP schemeassets.publishing.service.gov.uk, read 16 November 2026
  13. HM Government, Approved Document G, Sanitation, hot water safety and water efficiency, 2015 edition incorporating 2016 and 2024 amendmentsassets.publishing.service.gov.uk, read 16 November 2026
  14. HM Government, Approved Document L Volume 1, Dwellings, 2021 edition incorporating 2023 amendmentsassets.publishing.service.gov.uk, read 16 November 2026