In the Electrification of Heat trial, the measured SPF H2 came out below the design SCOP given to the household in 91.9% of properties. The mean gap was 0.66 and the median measured figure was 17.9% under the median design figure. A design SCOP printed as a single number can be read by the customer as a promise the heat pump then misses.
Three terms, three different things
COP is output over input at one operating point. SCOP is a calculated seasonal figure for a product at a stated flow temperature, worked out from part-load test results under BS EN 14825, and it is what design paperwork carries. SPF is measured on an installed heat pump over a year. The CIBSE Domestic Heating Design Guide 2026 draws the same line in section A.6.5: COP and SCOP describe the product on its own, while SPF describes the whole system, including emitters, flow temperature, hot water, defrost and controls. The homeowner version is in how a heat pump heats your home.
SPF needs a boundary. The Electrification of Heat performance report gives all three for the same 428 air source heat pumps: median 2.93 at H2, 2.88 at H3 and 2.78 at H4. That is 0.15 between H2 and H4 before anything about the design changes. An estimate that doesn't say which boundary it stands for can't be checked against a meter later. The H1 to H4 labels come from the European SEPEMO project, which the CIBSE guide cites for the point that the boundary has to be stated before an SPF can be compared with anything.
Seasonal performance factor (SPF) is heat delivered divided by electricity used over a year. The wider the boundary, the more electricity is counted, so H4 is lower than H2 for the same system. Boundaries as defined by the SEPEMO-Build project.
How the MCS estimate is worked out
The estimate an MCS installer must give before the contract is set by MCS 031 a). Issue 2.0 of the MCS:2025 version and Issue 5.0 for the original scheme, both dated 5 December 2025, use the same method:
- Take the space heating demand, hot water demand and total floor area from a valid EPC.
- Divide the space heating demand by 24 times the postcode's degree days to get a heat loss per kelvin, then multiply by the gap between 21°C and the postcode's outdoor low temperature. Dividing by floor area gives watts per square metre.
- Read an estimated SPF for space heating from the standard's emitter table, by that heat loss band and the proposed flow temperature. With existing radiators the flow temperature defaults to 60°C unless a room-by-room calculation justifies lower.
- Divide space heating demand by that SPF, and hot water demand by 1.9 (2.2 for ground source; it was 1.7 in earlier issues). Add any immersion top-up for pasteurising the cylinder.
- Show the total electricity as a range, 10% either side.
The standard itself says the annual demand is not for sizing the heat pump, and that a wider uncertainty of 25 to 30% would not be unreasonable in many cases. The 2025 version also lets you add an estimate from other software, as long as you explain its method, give it no more prominence than the MCS figure, and warn that it should be treated with caution if it is much better.
What the trial says about estimate against outcome
The 91.9% figure is the headline, but the finding underneath it is more awkward. The report found little correlation between design SCOP and measured SPF. Homes with a higher design figure did not reliably do better. So the design figures were high on average, and they also didn't rank the installs correctly. The report asks for a review of heat loss calculation, system design and efficiency estimation methods.
The measured spread is the other thing to carry into a quote. The middle half of the trial's air source heat pumps sat between 2.55 and 3.05 at H4. If your estimates for ordinary retrofits sit well above 3.05, it is worth being able to say what in the design justifies that.
Flow temperature, from two measured sources
The trial reports median COP at the H2 boundary by flow temperature, from 30-minute data across all its heat pumps: 3.50 at 35°C, 2.38 at 55°C and 2.02 above 65°C. Its mean operating flow temperature across air source and hybrid systems was 39.7°C.
Those two points give a slope. Dividing 2.38 by 3.50 and taking the same percentage fall for each of the 20 degrees between them gives about 1.9% lower COP for each extra degree of flow temperature. That is our arithmetic on the trial's figures, not a rate the report states.
OpenEnergyMonitor fitted a line through HeatpumpMonitor systems and publishes it: SPF H4 = 7.4189 minus 0.1008 times the heat-weighted average flow temperature in °C, with an R² of 0.515 and a 90% prediction interval of ±0.55. That works out at about 4.4 at 30°C, 3.9 at 35°C and 3.4 at 40°C. The page does not give the sample size, and it is a community analysis that has not been peer reviewed. The ±0.55 is as useful as the slope. Two systems at the same average flow temperature can sit half a point either side of the line.
We also grouped the site's rolling 365-day statistics on 15 November 2026 by each air source system's mean flow temperature while running, and took the median SPF of each group. These are self-selected, closely monitored homes, not typical installs. The groups include systems with less than a full year of data, so read it as indicative.
| Mean running flow temperature | Median SPF | Systems |
|---|---|---|
| 25 to 30°C | 4.33 | 44 |
| 30 to 35°C | 4.05 | 243 |
| 35 to 40°C | 3.65 | 180 |
| 40 to 45°C | 3.13 | 24 |
| 45 to 50°C | 2.60 | 5 |
Note that these are running averages over the year, not design flow temperatures. OpenEnergyMonitor's low flow temperature page reports that monitored systems designed at 45°C typically ran near 38.4°C on the coldest day, and those designed at 50°C near 40.0°C. The author says this fits the view that heat loss calculations often overestimate heat loss. Emitter sizing and flow temperature covers the design side.
Outdoor temperature and hot water pull the figure down
Median 30-minute COP at H4 for the trial's air source heat pumps peaked at 3.37 at 10°C outside and was 2.37 at -3°C and 2.30 at -5°C. It peaks at 10°C because above that the hot water share rises. A customer who checks their app in a cold week will see something well below the seasonal figure, which is the subject of our post on SCOP and winter.
Hot water runs at a lower efficiency than space heating in both of the datasets below. In the RHPP trial the median air source SPF H2 was 2.31 for hot water (284 sites) against 2.74 for space heating (292 sites). In our cut of 307 HeatpumpMonitor air source systems with separate hot water data (self-selected, closely monitored homes), the median hot water COP was 3.06 against 4.16 for space heating. A single blended SCOP hides that.
Presenting the estimate
Beside the number, put the boundary it stands for, the design flow temperature, whether hot water is included and the method that produced it. Then give a range, not a point. The trial's interquartile range was 0.50 wide at H4, and that was among homes designers had already judged suitable.
Say plainly that the figure is an estimate and that measured results in the national trial were usually lower than design figures. Record the estimate and its assumptions on the job so that a first-year comparison is possible. If the heat pump is metered, agree with the customer when you will look at the data together. Monitoring heat pump performance covers what to meter, and estimating running costs for customers carries the range through into pounds.