In the MEASURED project, survey-based BS EN 12831 calculations matched the measured heat loss in about 30% of 56 homes. They came out high in 59% and low in 11%. A measured figure is still not accepted in place of the calculation, and it does not tell you what each room needs. Its use today is as a check on the whole-house total.
What the heat transfer coefficient is
The heat transfer coefficient (HTC) is the rate of heat loss from the whole home per degree of difference between inside and outside, in W/K. It covers conduction through the fabric plus infiltration and ventilation. SAP and RdSAP predict it. A room-by-room calculation produces something comparable when you add up the rooms and divide by the design temperature difference.
The reference way to measure it is a co-heating test. The home is empty, electric heaters hold it at a steady temperature, and the power needed is logged against the temperature difference. That gives fabric and infiltration loss, and a blower door test is used to add ventilation. The government's SMETER evaluation notes that a co-heating test "can take a week or more". QUB is an alternative that takes less than a day. In that trial it tended to give lower HTCs than co-heating, with larger uncertainty, and it worked in 26 of the 30 homes.
What the SMETER trial found on accuracy
SMETER products estimate the HTC from smart meter data and indoor temperatures while people are living in the home. The Technical Evaluation of SMETER Technologies project, published by BEIS in January 2022, tested several against co-heating in 30 Halton Housing homes in north-west England. The measured HTCs ran from 127 to 269 W/K.
Each product declares a confidence interval with its result. Those intervals overlapped the measured HTC in 70% to 97% of homes, depending on the product, and the average declared interval ranged from 12% to 33%. Average bias (NMBE) ran from -0.7% to -26.9%, and scatter (CVRMSE) from 13.4% to 38.9%.
| Method | Average bias (NMBE) | Scatter (CVRMSE) | Homes |
|---|---|---|---|
| Switchee | -0.7% | 13.4% | 30 |
| Build Test Solutions | -2.1% | 15.2% | 30 |
| RdSAP by an expert assessor | -2.8% | 18.2% | 30 |
| RdSAP by a commercial assessor | -1.1% | 19.6% | 22 |
The two products in the table had declared intervals of ±21% and ±18%, which covered the measured value in 29 and 28 of the 30 homes.
RdSAP did almost as well as those two products in this sample, and the report says why that should not be generalised. These were small, simple homes of 38 to 83 m², built between about 1927 and 1990, all with gas combi boilers, assessed by a very experienced assessor. The sample had one detached house, ten semis and 19 end-terraces. There were no flats, no mid-terraces and no heat pumps. The report expects typical commercial RdSAP to be worse, and adds that the effect of party-wall heat transfer on a measured HTC is "still not fully understood".
What DEEP and MEASURED found against calculation
The DEEP field trial ran over 40 co-heating tests, 400 heat flux measurements and 200 air tests on 14 solid-walled homes between 2019 and 2024. EPCs overestimated the measured heat loss by 42% on average, more before retrofit than after. They overpredicted retrofit savings by 46% on average. When the EPC defaults were replaced with measured airtightness, U-values and thermal bridging, the overprediction of savings fell to between 17% and 27%. Dynamic simulation overpredicted heat loss by between under 1% and 13%, depending on the inputs.
Set beside SMETER, the two trials pull differently. RdSAP was nearly unbiased in small, simple homes and 42% high in solid-walled ones. On this evidence the size of the error depends on the kind of house, and solid walls are where defaults are furthest from measurement. Assumed and measured U-values has the wall figures.
MEASURED is the study closest to heat pump design, because it compared the BS EN 12831 survey method with measurement. It was government-funded (£233,888) and run by Build Test Solutions with Veritherm and Elmhurst. The 30%, 59% and 11% split above is its headline. Build Test Solutions, which led it, also sells measurement services. The case study explains why a measured HTC cannot yet replace the survey. MCS requires BS EN 12831, which allows measured air permeability and U-values but has no route for a whole-house HTC, and a whole-house figure would still need an agreed way to apportion it to rooms. A CIBSE working group has been set up to look at updating the method.
A second DESNZ-funded project, Right Sizing Heat Pumps, led by Hoare Lea and published in July 2025, used room temperature sensors and smart meter data in 30 homes plus tests at the Salford Energy House. The team is exploring commercial use of the tool it built. The project reports that its tool sized heat pumps consistently 15 to 20% smaller than the MCS Heat Load Calculator. It reports a predictive error of 9% for its dynamic model and 16% for a steady-state one, needing about 10 days and 3 weeks of data respectively, or at least 2,000 degree hours in blocks of 12 hours or more. It also says such a remote assessment does not conform to current MCS standards or BS EN 12831, and a CIBSE technical memorandum is being written.
Using a measured figure as a cross-check
A room-by-room calculation does two jobs. It sizes the heat pump from the total, and it sizes each emitter from the room figure. A measured HTC can only test the first. The CIBSE Domestic Heating Design Guide (version 2026-02, section 2.5) takes the same position: whole-house measurements based on energy use or temperature decay are useful as a cross-reference for the heat generator sizing figure, but not a substitute, because they do not give the room losses needed to size the system.
To compare, multiply the measured HTC by the design temperature difference you used. A home measured at 200 W/K with a 23 °C difference would need 4.6 kW. Then set that beside the calculated total, having checked that both include the same things. A co-heating HTC is fabric plus infiltration unless ventilation has been added. A design total may include allowances that a steady-state measurement does not.
Carry the uncertainty through. A result of 200 W/K with a declared interval of ±20% is a range of 160 to 240 W/K, or 3.7 to 5.5 kW at that temperature difference. If the calculated total falls inside the range, the check has passed and has told you little more. If it falls well outside, look at the inputs with the largest known errors: wall U-values, the air change rate, and party walls.
Without a measurement, annual gas use gives a rougher version of the same check. The method is in heat loss surveys and choosing the right size, and our post on uncertainty in heat pump sizing follows one case through.
What to record
Note the method and product, the monitoring period, the result with its declared interval, and whether the home was occupied. Record the calculated total it was compared with, and what you changed as a result, input by input. A measured HTC that leads you to lower a wall U-value is evidence for that change. The design still rests on the room-by-room calculation.