The government's DEEP research found that internal wall insulation introduced a risk of interstitial condensation in solid-walled homes. It also found that aiming for a wall U-value of about 0.8 W/m²K, not the Building Regulations value of 0.3, reduced that risk while keeping about two-thirds of the energy saving. Both findings are in the DEEP Synthesis Report, published by DESNZ in October 2024 with its technical reports.
Approved Document L allows for this. In the 2021 edition, which applies in England until the 2026 edition takes effect on 24 March 2027 (subject to the transitional arrangements in Circular Letter 01/2026), Table 4.3 gives 0.30 W/m²K as the improved value for a wall insulated internally or externally, and paragraph 4.13 says an upgraded element should generally be no worse than 0.7, with a lesser standard acceptable where the work complies with Part C on interstitial and surface condensation. Paragraph 0.20 makes the same point and points to Approved Document C, and a note to Table 4.3 allows a lesser standard where meeting it would cut a room's floor area by more than 5%. In the 2026 edition, which applies from 24 March 2027, the Part C link is paragraph 0.22.
Where the risk sits in an insulated solid wall
An uninsulated solid wall is warmed by the room. Put insulation on the inside and the masonry behind it runs colder, because less heat reaches it. Water vapour from the room that gets past the insulation meets that colder surface, and if the surface is cold enough the vapour condenses there, inside the wall, where nobody can see it. The more insulation, the colder the masonry, which is why a more modest U-value target carried less risk in DEEP.
Leaving the wall alone is not risk-free either. DEEP found uninsulated solid-walled homes were themselves at risk of surface condensation, and that solid wall insulation was the measure that reduced it most. The risk remained at discontinuities, where the insulation stops or is interrupted, until a whole-house approach removed them.
DEEP's teams also commonly found polystyrene-backed plasterboard left from earlier retrofits, and reported that it presented an interstitial condensation risk. A wall that looks untouched may already have been lined.
What DEEP's moisture modelling showed
DEEP Report 6.03, by Loughborough University, simulated a solid brick wall over ten years of recorded weather in London and Manchester with a validated hygrothermal tool. It measured relative risk as the number of days the humidity at the junction of insulation and masonry stayed above 80%.
- Internal insulation always increased the risk against the uninsulated wall, even a thin layer reaching only 1.1 W/m²K.
- More insulation meant more risk in every case, and the report found no safe threshold. With wood fibre, the risk rose faster below about 0.8 W/m²K, reached with 30 mm of board. In the modelling, 0.8 cut space heating demand by about 20%, against about 30% at 0.3.
- In DEEP's computer model of a solid brick wall, vapour-open wood fibre carried the lowest risk. Expanded polystyrene with an air and vapour control layer carried more. Taking the layer out lowered the modelled risk because the wall could dry inwards, but the layer is there to keep room moisture out of the wall, so whether to fit one is a decision for a moisture risk assessment of the actual wall, not a rule of thumb.
- Manchester, with more wind-driven rain and less drying, came out worse than London. A water-repellent brick cream only helped where the risk was already high.
- Homes with more moisture from cooking, bathing and laundry had higher risk, and results were sensitive to indoor humidity. The report links this to ventilation, and recommends ten years of weather data over a single year.
What the assessment methods can show
BS 5250:2021, "Management of moisture in buildings: Code of practice", is the UK code for this assessment. BSI describes it as replacing BS 5250:2011+A1:2016 and taking a whole-building approach, looking at how moisture controls interact instead of treating each one alone.
Two calculation methods sit behind most assessments, and CIBSE Guide A (section 7.7) explains the difference. The Glaser method of BS EN ISO 13788 treats the wall as flat layers, applies monthly mean conditions inside and out, and predicts condensation wherever the calculated vapour pressure exceeds saturation, adding the months up to see whether moisture accumulates over the year. It assumes moisture moves only by vapour diffusion, with constant material properties. Guide A lists what that leaves out: moisture storage in the materials, capillary movement of liquid water, air leakage through the structure, rain, and the way a wet material conducts heat better. It concludes the method is less suitable for components that store significant water. A solid masonry wall is one.
Full hygrothermal models to BS EN 15026 run hourly and account for moisture storage, capillary transport and the effect of moisture on conductivity (Guide A, section 7.7.4). They need good material data and someone who knows how to use them.
DEEP adds a caution about how results get used. The synthesis report found pass or fail risk assessments "too simplistic" on their own, because risk is continuous: a wall just above a threshold is little different from one just below it. A pass does not mean the wall will stay dry in every winter with every household.
Wet walls lose more heat
In BRE's in-situ study, adding measured brick moisture content and density to the calculation brought calculated U-values closer to measured ones for some of the 18 solid walls examined, though not all. A wet wall loses more heat than a dry one, so anything that leaves the masonry wetter also works against the insulation. Guide A makes the same physical point from the other direction: thermal conductivity depends on moisture content, which is one reason the simple Glaser method can mislead on masonry.
Those are the effects a diffusion-only calculation leaves out, so on an older solid wall, ask whoever does the assessment which method they are using, and which weather data. Older and listed homes covers listing and consent.
Checks before insulating a solid wall
- Deal with water that is already getting in. The government's damp and mould guidance for England separates condensation damp from penetrating damp, rising damp and damp from leaks or floods. Insulation does not fix the last three.
- Find out what is on the wall now, including any earlier dry-lining with polystyrene-backed board.
- Set the target U-value with the moisture assessment, not before it. DEEP's 0.8 W/m²K result, and Approved Document L's allowance for a lesser standard under Part C, are reasons to treat 0.3 as a question for the assessment.
- Ask which board and finish are proposed. In DEEP's modelling, vapour-open systems carried less risk, and the synthesis report warns that vapour-impermeable paint may undo that.
- Mark every place the insulation will stop or be interrupted, and decide what happens there. DEEP's residual risks were at these points.
- Agree which assessment method is being used, who is doing it, and what inputs it assumes for weather, materials and occupancy.
- Count the measure for ventilation. In England, Approved Document F classes wall insulation to more than 50% of the external wall area as a major measure, which can change the ventilation the home needs. See ventilation when upgrading fabric.
- Check for listing before any design work.
- Allow for repairs. In DEEP, repairs and enabling work added 26% to retrofit costs on average.
What to carry into the heat loss calculation
Use the U-value the wall will have after the work, as designed, in the room-by-room calculation. If the moisture assessment lands on 0.8 W/m²K, a calculation that assumes 0.3 will undersize the emitters in those rooms. Where insulation stops at a discontinuity, the uninsulated area keeps its old value. Assumed and measured U-values covers what the starting value of a solid wall is likely to be.