The largest UK trial measured air source heat pumps producing a median of 2.78 units of heat for each unit of electricity over a year. That is the Electrification of Heat project, and the figure is the seasonal performance factor (SPF) at the H4 boundary for 428 air source heat pumps. Open monitoring data from self-selected, closely monitored homes on HeatpumpMonitor.org shows higher figures than the national trial's median of 2.78 at H4. Both are measured, but they describe different groups of homes.
What the Electrification of Heat trial measured
The government-funded Electrification of Heat project installed 742 heat pump systems across Great Britain through three contractors, in north-east England, south-east England and south-east Scotland. The last was installed in November 2021 and, for most homes, monitoring ran until 28 September 2023. Energy Systems Catapult published the final performance report in December 2024. Each home's SPF covers a 12-month window.
SPF is heat supplied divided by electricity used over a year. The answer depends on which electricity you count, so trials state a boundary. H2 counts less of the equipment than H4, so H4 is always the lower number.
Seasonal performance factor (SPF) is heat delivered divided by electricity used over a year. The wider the boundary, the more electricity is counted, so H4 is lower than H2 for the same system. Boundaries as defined by the SEPEMO-Build project.
For the 428 air source heat pumps with usable data:
| Boundary | Median SPF | Middle half of homes |
|---|---|---|
| H2 | 2.93 | 2.67 to 3.19 |
| H4 | 2.78 | 2.55 to 3.05 |
The spread matters as much as the median. A quarter of homes were below 2.55 at H4 and a quarter were above 3.05.
House type and age made no significant difference
The report found minor differences but no statistically significant variation in SPF H4 by house type or by age band.
The report adds its own caution. Designers had judged every one of these homes suitable before the heat pump went in, so the sample is not the whole housing stock. It shows that age and type did not predict performance among homes that got a heat pump. It does not show that every home is suitable.
Measured performance fell short of the design figure
Each household was given an "as designed" seasonal efficiency (SCOP) before installation. In 91.9% of properties the measured SPF H2 was lower. The mean gap was 0.66, and the median measured figure was 17.9% below the median design figure. There was little correlation between the two, so a higher design figure did not reliably mean a better result. The report calls for a review of how heat loss, system design and efficiency are estimated. SCOP, SPF and performance estimates covers what that means for a quote.
Flow and outdoor temperature both mattered
Flow temperature, the temperature of the water sent to the radiators, showed the clearest pattern. The report measured efficiency over half-hour periods (the coefficient of performance, COP). Across all the trial's heat pumps the median COP at the H2 boundary was 3.50 when the flow was 35°C, 2.38 at 55°C and 2.02 above 65°C. The mean operating flow temperature across the air source and hybrid heat pumps was 39.7°C.
Outdoor temperature mattered too. For air source heat pumps the median half-hour COP at H4 peaked at 3.37 when it was 10°C outside, and fell to 2.37 at -3°C and 2.30 at -5°C, which the report calls common GB design conditions.
Heat pumps in gas hybrid systems did less well. Their 94 heat pumps had a median SPF H4 of 2.50, and the less of the heating they did, the lower their efficiency tended to be.
The older RHPP trial was lower
The RHPP analysis, published by BEIS in March 2017, monitored 700 sites from 31 October 2013 to 31 March 2015. The heat pumps had been installed between 2009 and 2014. In its main analysis sample the median air source SPF was 2.65 at H2 (292 sites) and 2.44 at H4 (293 sites, middle half 2.15 to 2.67).
So the median at H4 rose from 2.44 to 2.78 between the two trials, which the Electrification of Heat report describes as around 0.3. The spread did not narrow: the report puts the interquartile range in both trials between 0.50 and 0.62. One caveat on the older figure: the heat meters were calibrated for water rather than glycol, which the authors say affects many sites and over-states SPF by 4 to 7%. They did not apply a correction.
HeatpumpMonitor shows what good systems reach
HeatpumpMonitor.org is an open site run by the OpenEnergyMonitor community where owners and installers publish metered data from their own systems. On 15 November 2026 its public list held 869 systems, 853 of them air source.
Its rolling 365-day statistics show higher figures than the trial's median of 2.78 at H4, but the sample is self-selected. People who fit a heat meter and publish the results are mostly enthusiasts and installers who design for low flow temperatures. The data shows what careful design reaches. It is not a national average, and it should not be quoted as one.
What none of them show
None of these is a sample of heat pumps being installed now. The trial installs finished in 2021, and published measured SPF data for recent Boiler Upgrade Scheme installs is limited.
The trial also says little about ground source. Only 23 ground source systems were analysed, and the report says not to use it as a reference for them.
The trials report what happened, and are thinner on why any one home did well or badly. Other work fills in some of that. Nesta and Bristol City Council drew on 92 technical audits of social housing installs, published in October 2026, and every audit found at least one design, installation or commissioning fault.
For a homeowner, the practical reading is to ask what flow temperature a design assumes and how the installer will check the result. Monitoring heat pump performance covers the installer's side of that.